Feedwater - ASME Consensus on Operating Practices

Drum Operating Pressure (psig)
Feedwater 0-300 301-450 451-600 601-750 751-900 901-1000 1001-1500 1501-2000
Diss. Oxygen <40ppb <40ppb <7ppb <7ppb <7ppb <7ppb <7ppb <7ppb
Total Iron <100ppb <50ppb <30ppb <25ppb <20ppb <20ppb <10ppb <10ppb
Total Copper <50ppb <25ppb <20ppb <20ppb <15ppb <15ppb <10ppb <10ppb
Hardness <300ppb <300ppb <200ppb <200ppb <100ppb <50ppb - Not Detectable-
pH 7.5-10.0 7.5-10.0 7.5-10.0 7.5-10.0 7.5-10.0 8.5-9.5 9.0-9.6 9.0-9.6

Note: These feedwater guidelines are based on achieving steam purity required for superheaters, turbines, or process restrictions. Many plants operate outside of these criteria. For specific recommendations ask our water treatment experts.

Boiler Water - ASME Consensus on Operating Practices

Drum Operating Pressure (psig)
Boiler Water 0-300 301-450 451-600 601-750 751-900 901-1000 1001-1500 1501-2000
Silica <150ppm <90ppm <40ppm <30ppm <20ppm <8ppm <2ppm <1ppm
Total Alkalinity <350ppm <300ppm <250ppm <200ppm <150ppm <100ppm --Not Specified--
Conductivity <3500 <3000 <2500 <2000 <1500 <1000 <150 <100
Free Hydroxide -----------------Not Specified----------------- ---Not Detectable---

Note: These Boiler water guidelines are based on achieving steam purity required for superheaters, turbines, or process restrictions. Many plants operate outside of these criteria. For specific recommendations please ask our water treatment experts.