|
Boiler
Water Treatment Considerations
For
prolonged boiler life, a water
treatment program recommended by
Thermidaire is a must. Steam
boilers are sensitive to even
minor deposits on tube walls.
Therefore, most feedwater
treatment programs are oriented
toward scale control. However,
internal corrosion control
cannot be ignored. Scald with
locally high caustic
concentrations can develop on
metal components, strip away the
protective magnetite film, and
attack the base metal. This
attack is characterized by
gouging of the metal and its
severity is directly
proportional to increasing
operating pressures.
Oxygen
is highly corrosive when
dissolved in water, and can
result in corrosion pitting of
heat transfer surfaces.
Mechanical deaeration of the
feed water using a deaerator is
the typical first step in
eliminating dissolved oxygen and
other gases such as ammonia and
carbon dioxide. Mechanical
deaeration will reduce oxygen to
as low as 0.005 cc/liter. In
boilers below 1,000 psig, the
oxygen-scavenging chemical is
fed continuously, preferably at
the storage compartment of
deaerator or at suction of
boiler feed pump, to provide
turbulence and time for mixing.
Specification of chemicals and
dosages should be in accordance
with the recommendations of the
Owner's water consultant.
Generally,
a total water treatment program
should pursue the following
four-point goal:
1.
Maintenance of free caustic
corrosion potential,
accomplished by eliminating free
hydroxide (caustic) though the
addition of various phosphate
salts.
2.
Minimize caustic deposit
formation due to scale and
suspended solids by
chelation
and sludge conditioners so that
blowdown will remove this
potential problem.
3.
Eliminate oxygen content through
deaeration or other mechanical
means and chemical scavenging.
4.
Prevention of carryover and
foaming.
The
accomplishment of these
objectives generally requires
treatment before and after
introduction of water into the
boiler. The selection of
pre-treatment processes depends
upon water source, chemical
characteristics, amount of
make-up water needed, plant
operating practices, etc. These
treating methods include
filtering, softening,
demineralizing, deaerating, and
preheating.
After-treatment
involves the addition of
chemicals into the boiler water.
This after-treatment is required
to compensate for any variations
in the pre-treatment of the
boiler feedwater system and to
assure the ultimate protection
of the boiler. Because of the
variables involved, no one
"boiler compound"
cannot be considered a cure-all,
nor is it advisable to
experiment with homemade
treating methods. Sound
recommendations and their
employment should be augmented
by periodic analysis of the raw
water, boiler water, and
condensate.
Feedwater
Quality Limits
The
ABMA specifies limits, as listed
in Figure 5, for boiler water
composition with respect to
operating pressure to assure
good quality steam. While there
are other considerations (such
as corrosion and deposit
formation) in establishing
boiler water composition, the
limits indicate that
requirements for feedwater
purity become more stringent as
operating pressure increases.
|
Drum
Pressure, psig
|
Range
Total Dissolved Solids 1
Boiler Water PPM
|
Range
Total Alkalinity 2,6
|
Suspended
Solids Boiler Water PPM
|
Range
Total Dissolved Solids
2,4 Steam PPM (max
expected value)
|
|
0
- 300
|
700
- 3500
|
140
- 700
|
15
|
0.2
- 1.0
|
|
301
- 450
|
600
- 3000
|
120
- 600
|
10
|
0.2
- 1.0
|
|
451
- 600
|
500
- 2500
|
100
- 500
|
8
|
0.2
- 1.0
|
|
601-
750
|
200
- 1000
|
40
- 200
|
3
|
0.1
- 0.5
|
|
751
- 900
|
150
- 750
|
30
- 150
|
2
|
0.1
- 0.5
|
|
901
- 1000
|
125
- 625
|
25
- 125
|
1
|
|
|
1001
- 1800
|
100
|
Note3
|
1
|
0.1
|
|
1801
- 2350
|
50
|
Note3
|
Not
Applicable
|
0.1
|
|
2351
- 2600
|
25
|
Note3
|
Not
Applicable
|
0.05
|
|
2601-
2900
|
15
|
Note3
|
Not
Applicable
|
0.05
|
Notes:
1.
Actual values within the range
reflect the TDS in the feedwater.
Higher values are for high
solids, lower values are for low
solids in the feedwater.
2.
Actual values within the range
are directly proportional to the
actual value of TDS of boiler
water. Higher values are for
high solids, lower values are
for low solids in the boiler
water.
3.
Dictated by boiler water
treatment.
4.
These values are exclusive of
silica.
5.
Expressed as equivalent calcium
carbonate in PPM.
ABMA
Boiler Quality
Improper
and nonexistent feedwater
treatment is the major factor
causing boiler failure, which
ultimately results in boiler
down time and costly repairs.
All fresh water available from
natural sources requires varying
degrees of treatment prior to
use in a boiler. The impurities
in fresh water ware many and
each required special attention.
Solids in the form of minerals,
chemicals, and organic material
are all found in fresh water and
all have a different effect on
the internal surfaces of a
boiler.
Boiler
feedwater treatment by a
competent water treating company
will result in prevention of
scale and deposits, removal of
dissolved gases (free oxygen),
protection against corrosion,
elimination of carry-over of
water with steam, maximum boiler
efficiency, and maintenance
savings. It is imperative that
the Owner contacts a company
specializing in boiler feedwater
treatment and obtain their
recommendation and service.
Failure
to heed the above warning will
cause excessive damage to the
boiler. It will be very costly
to repair this damage to the
boiler and place it back in
proper condition. The warranty
does not cover this type of
maintenance. This is the Owner's
responsibility.
|