Products Menu       
FAQ Site Map Search Tools
Environment FriendlyAsk ExpertsABChemicals

  Information    


Suggested Maintenance Log Program

The following maintenance items, as appropriate to the specific boiler system, need to be considered for implementation on a regular basis (e.g., daily, weekly, monthly, semiannually, annually). A checklist of the items should be incorporated into a maintenance log with provisions for checking off the item for the appropriate period. A separate log sheet is suggested for each period. The log sheets can be filed in a loose-leaf binder, and should be retained as a permanent maintenance record.

The log sheets can be used as a handy check-off system when establishing a facility maintenance program. In all cases the equipment manufacturer's recommendations should be followed.

DAILY

  • Blow down and test low water cutoffs of steam boilers (once per shift for high pressure)
  • Blow down gage glasses (steam)
  • Blow down make up feeder (low pressure steam)
  • Blow down boiler (steam)
  • Check boiler contraol linkage
  • Check boiler and system for leaks
  • Check burner flame

WEEKLY

  • Check compressor (s) lubricating oil level (control and atomizing)
  • Check flame signal strength for both pilot and main flame, and record readings
  • Check flame failure cutoff and timing
  • Check pilot and main flame fuel shutoff valve closing
  • Check ignitor and burner operation
  • Check level in chemical treatment tank

MONTHLY

  • Check compressor (s) air filter, and clean or replace as required
  • Check boiler water treatment test results received from treatment company, adjust treatment as required
  • Lubricate motor and equipment bearings
  • Test fan and air pressure interlocks
  • Check main burner fuel safety shutoff valves for leakage
  • Check low fire start interlock
  • Check high pressure/temperature interlocks
  • Test low water cutoffs (hot water)
  • For oil -- test pressure and temperature interlocks
  • For gas -- test high and low gas pressure interlocks
  • Manually lift safety/safety relief valves and check operation

SEMIANNUALLY

  • Inspect burner components
  • Check flame failure system components
  • Check piping and wiring of all interlocks and shutoff valves
  • Recalibrate all indicating and recording gages and instruments
  • Perform a slow drain test for low water cutoffs (steam)
  • Check combustion control system
  • For oil -- check atomizers and strainers
  • Test boiler safety/safety relief valves in accordance with ASME Boiler and Pressure Vessel Code, Sections VI and VII

ANNUALLY

  • Perform the SEMIANNUAL maintenance procedures
  • Check all equipment coils and diaphragms
  • Perform a pilot turndown test
  • Recondition or replace low water cutoff
  • For gas -- check drip leg and gas strainer
  • Clean boiler firesides
  • Drain boiler, open manholes and hand holes, and clean watersides
  • Have boiler inspected by a commissioned inspector
  • Clean burner and gans
  • Replace gaskets
  • Leak-test all fuel valves
  • Test operation of all controls and safety devices
  • Have fuel-burning system adjusted using combustion test instruments

AFTER EACH PERIOD

  • Make a record of all maintenance and parts replacement in the maintenance log