ORGANIC WATER TREATMENT CHEMICALS
STEAM BOILERS, COOLING TOWERS,
HOT AND CHILLED CLOSED SYSTEMS
FUEL OIL TREATMENT
BOILER HP
VS MAKE-UP
|
Boiler
Horse Power
|
Percent
of Condensate Return
|
|
(hp)
|
0%
|
10%
|
20%
|
30%
|
40%
|
50%
|
60%
|
70%
|
80%
|
90%
|
|
40
|
160
|
144
|
128
|
112
|
96
|
80
|
64
|
48
|
32
|
16
|
|
60
|
240
|
216
|
192
|
168
|
144
|
120
|
96
|
72
|
48
|
24
|
|
80
|
320
|
288
|
256
|
224
|
192
|
160
|
128
|
96
|
64
|
32
|
|
100
|
400
|
360
|
320
|
280
|
240
|
200
|
160
|
120
|
80
|
40
|
|
125
|
500
|
450
|
400
|
350
|
300
|
250
|
200
|
150
|
100
|
50
|
|
150
|
600
|
540
|
480
|
420
|
360
|
300
|
240
|
180
|
120
|
60
|
|
200
|
800
|
720
|
640
|
560
|
480
|
400
|
320
|
240
|
160
|
80
|
|
250
|
1000
|
900
|
800
|
700
|
600
|
500
|
400
|
300
|
200
|
100
|
The
above figures are given as examples.
Other boiler sizes can be computed
accurately by using the
following formula;
hp
x 4 gallons/hr - % condensate
return = makeup water in gallons/hour
|