|
Organic
Water Treatment Chemicals
Steam Boilers, Cooling Towers,
Hot And Chilled Closed Systems
Fuel Oil Treatment
(Home of D.M Concentrate)
Neutral
pH Cleaning Procedure – Closed
Circuits
- Determine
the volume of the system to
be cleaned
- Pump
water from the sump until it
is clear and free of
suspended iron
- Slug
feed the neutral cleaner pH
to the sump – a 10%
solution is preferred for
cleaning
- Circulate
the cleaner for 1 to 10 days
- Sample
the system every 3 hours on
the first day and test for
dissolved and suspended iron
- Thereafter
sample the system twice per
day and test for dissolved
and suspended iron
- If
the total iron concentration
reaches 8,000 ppm dump the
cleaning solution and repeat
the cleaning procedure
- Samples
should also be tested for pH
– the pH will rise during
the cleaning process
- When
the solution pH reaches pH
7.5 slug feed a 10 - 20%
citric acid solution to
neutralize
- When
the iron concentration
reaches a plateau the
cleaning is finished
- Pump
the cleaning solution out of
the system. Flush the system
and then replace with fresh
make up
- Add
a molybdate or nitrite based
inhibitor product to the
system
If
you can raise the temperature of
the circulating water to as high
as 140 F it will speed up the
cleaning. Keeping the pH of the
cleaning solution between pH 7.0
and 7.5 will minimize the time
required for cleaning. Be sure
to discuss disposal of the spent
cleaning solution with the
customer. The neutral pH cleaner
is not hazardous but you need to
check disposal regulations
before dumping it on the ground.
If
the cleaning is carried out at
chilled water temperature (40 F)
it may take several weeks but it
still can be effectively
completed. This means that the
system can be effectively
cleaned on line. However, for on
line cleaning water must be
continuously bled from the
system until the inhibitor
concentration has been
completely depleted and the bulk
of the suspended iron has been
removed from the circulating
water.
|