EG-900-101
DESCRIPTION: A colorless, low-volatile,
hydroscopic liquid used as an
antifreeze in cooling tower
systems.
APPLICATION: Use as antifreeze for
protection of cooling towers or
closed systems against severe
weather conditions.
DIRECTIONS: The following Glycol/Water ratios should be used to
provide protection at these
water temperatures:
Temperature
+10oF
0oF
-10oF
Ethylene
Glycol
25%
32%
38%
Water
75%
68%
62%
EXAMPLE:
To protect system to 10oF,
add 25 gallons of glycol for
every 75 gallons of system
water.
*NOTE:
It is recommended to add ACE
Closed System Treatment at
the rate of 1 gallon CST
to each 100 gallon of system
water (glycol/water).
SAFETY
DATA: Contains
Ethylene Glycol.
Avoid skin/eye contact.
Do not ingest. KEEP OUT OF
THE REACH OF CHILDREN.
FIRST
AID:
For
eyes, wash with plenty of
water for fifteen minutes. GET IMMEDIATE MEDICAL
ATTENTION.
For
skin, wash skin with soap
and water.
Get medical help if
irritation persists.
For
inhalation, remove to fresh
air.
For ingestion, drink
water and induce vomiting. GET IMMEDIATE MEDICAL
ATTENTION.
PACKAGING:
5 gal & 45 gal units