Products Menu       
FAQ Site Map Search Tools
Environment FriendlyAsk ExpertsABChemicals

  Information    


Organic Water Treatment Chemicals
Steam Boilers, Cooling Towers, Hot And Chilled Closed Systems
Fuel Oil Treatment
(Home of D.M Concentrate)

Locating Water Losses in Closed Systems

THE PROBLEM

Closed heating and cooling water systems typically require little make up water and minimal treatment chemical additions following the initial system charge. However, when leaks occur they can be costly and make it difficult to maintain treatment levels necessary for good corrosion and deposit control.
The source(s) of significant water losses should be identified and eliminated. This will help improve treatment program effectiveness, lower operating costs, and reduce the potential for unexpected system failure.

VERIFYING WATER LOSS

Routine testing of the conductivity, pH or alkalinity, and inhibitor level is generally used to determine if there has been a water loss. If these parameters decrease simultaneously, water has been lost. If the water loss is significant (> 1 gpm), a ¾" water meter installed on the make up line (on a by-pass) can help quantify the rate of water loss.

POSSIBLE CAUSES

The following checklist may help identify why a closed system is losing water:
1) Check all circulating pumps for leaks around the seals or packing. Replace and/or tighten if necessary.

2) Check the expansion tank to ensure it is not full of water. If the expansion tank does not have sufficient air space for expansion when the system water heats up, the relief valve will lift to relieve the excess pressure. If the tank is full of water, manually drain so that it is only about 1/3 full when the system is cold.

3) Check all pressure relief valves. Be aware that closed systems can intermittently relieve excess system pressure due to temperature changes and an improperly functioning pressure regulator, located on the make up line. If the regulator fails, the system pressure can slowly increase to the point where the pressure relief valve momentarily opens. Water will then be expelled until the pressure returns to normal.

You can check for a defective pressure regulator by installing a pressure gauge before and after the regulator. The pressure reading after the pressure regulator should not exceed the preset pressure setting on the regulator. If it does, the pressure regulator is defective and should be replaced. Note that the pressure setting (fixed regulator) or the pressure range (adjustable regulator) will be indicated on a metal tag attached to the regulator and that the regulator should be set at 2 psig above the highest head in the system.
Since the system pressure can change with the temperature, make sure the temperature is stable when checking the pressure regulator. For example, a hot water system at room temperature with the circulating pumps off may have a pressure of only 12 psig. With the pumps on and the water heated to 160 F, the pressure may increase to as high as 28 psig.

4) Check all automatic air vents to see if they are leaking water. Pay particular attention to vents, which are piped, directly into a drain. Replace all air vents that are leaking water.

5) Check the back flow preventers. If the make up line does not have a properly installed and functioning back flow preventer and if the system pressure is greater than the make up line pressure, system water can be lost into the make up line. Swing type check valves are not acceptable since they will not function properly under a vacuum - as water rushes from the closed system (higher pressure) to the make up line (lower pressure), a vacuum can occur. A common cause of the system pressure being greater than the make up line pressure is when someone shuts off the main water supply outside a building or down the street. Note that all new buildings have back flow preventers on the main potable water supply line. Each closed system should have its own back flow preventer.

6) Where fan coil units are used with a chilled water system, check the conductivity, pH, inhibitor level, hardness or color (if a colored treatment product or a dye is used) of the water in the condensate drain pans. If a fan coil unit is leaking, you will detect the presence of treatment chemicals and/or hardness in the drain pan water. Otherwise, the drain pan water should be more or less distilled water (<25 umhos).

7) Where steam is used to heat a hot water system (via a heat exchanger), check for contamination in the various boiler system waters. If there is a leak in the heat exchanger, water from the hot water loop will generally leak into the boiler system via the condensate return. This contamination may be reflected in the conductivity, color, hardness, or sulfite level (lowered) of the condensate, feed water, or boiler water.

Home - Contact - About us - Products - Services - Policy - Forms - Info - Site Map - Search

Add this site to your favorites

Copyright 2003, Thermidaire Corporation Canada Limited. All rights reserved.