|
Organic Water Treatment
Chemicals
Steam Boilers, Cooling Towers,
Hot And Chilled Closed Systems
Fuel Oil Treatment
(Home of D.M Concentrate)
Locating
Water Losses in Closed Systems
THE
PROBLEM
Closed
heating and cooling water
systems typically require little
make up water and minimal
treatment chemical additions
following the initial system
charge. However, when leaks
occur they can be costly and
make it difficult to maintain
treatment levels necessary for
good corrosion and deposit
control.
The source(s) of significant
water losses should be
identified and eliminated. This
will help improve treatment
program effectiveness, lower
operating costs, and reduce the
potential for unexpected system
failure.
VERIFYING
WATER LOSS
Routine
testing of the conductivity, pH
or alkalinity, and inhibitor
level is generally used to
determine if there has been a
water loss. If these parameters
decrease simultaneously, water
has been lost. If the water loss
is significant (> 1 gpm), a
¾" water meter installed
on the make up line (on a
by-pass) can help quantify the
rate of water loss.
POSSIBLE
CAUSES
The
following checklist may help
identify why a closed system is
losing water:
1) Check all circulating
pumps for leaks around the seals
or packing. Replace and/or
tighten if necessary.
2)
Check the expansion tank to
ensure it is not full of water.
If the expansion tank does not
have sufficient air space for
expansion when the system water
heats up, the relief valve will
lift to relieve the excess
pressure. If the tank is full of
water, manually drain so that it
is only about 1/3 full when the
system is cold.
3)
Check all pressure relief
valves. Be aware that closed
systems can intermittently
relieve excess system pressure
due to temperature changes and
an improperly functioning
pressure regulator, located on
the make up line. If the
regulator fails, the system
pressure can slowly increase to
the point where the pressure
relief valve momentarily opens.
Water will then be expelled
until the pressure returns to
normal.
You
can check for a defective
pressure regulator by installing
a pressure gauge before and
after the regulator. The
pressure reading after the
pressure regulator should not
exceed the preset pressure
setting on the regulator. If it
does, the pressure regulator is
defective and should be
replaced. Note that the pressure
setting (fixed regulator) or the
pressure range (adjustable
regulator) will be indicated on
a metal tag attached to the
regulator and that the regulator
should be set at 2 psig above
the highest head in the system.
Since the system pressure can
change with the temperature,
make sure the temperature is
stable when checking the
pressure regulator. For example,
a hot water system at room
temperature with the circulating
pumps off may have a pressure of
only 12 psig. With the pumps on
and the water heated to 160 F,
the pressure may increase to as
high as 28 psig.
4)
Check all automatic air vents to
see if they are leaking water.
Pay particular attention to
vents, which are piped, directly
into a drain. Replace all air
vents that are leaking water.
5)
Check the back flow preventers.
If the make up line does not
have a properly installed and
functioning back flow preventer
and if the system pressure is
greater than the make up line
pressure, system water can be
lost into the make up line.
Swing type check valves are not
acceptable since they will not
function properly under a vacuum
- as water rushes from the
closed system (higher pressure)
to the make up line (lower
pressure), a vacuum can occur. A
common cause of the system
pressure being greater than the
make up line pressure is when
someone shuts off the main water
supply outside a building or
down the street. Note that all
new buildings have back flow
preventers on the main potable
water supply line. Each closed
system should have its own back
flow preventer.
6)
Where fan coil units are used
with a chilled water system,
check the conductivity, pH,
inhibitor level, hardness or
color (if a colored treatment
product or a dye is used) of the
water in the condensate drain
pans. If a fan coil unit is
leaking, you will detect the
presence of treatment chemicals
and/or hardness in the drain pan
water. Otherwise, the drain pan
water should be more or less
distilled water (<25 umhos).
7)
Where steam is used to heat a
hot water system (via a heat
exchanger), check for
contamination in the various
boiler system waters. If there
is a leak in the heat exchanger,
water from the hot water loop
will generally leak into the
boiler system via the condensate
return. This contamination may
be reflected in the
conductivity, color, hardness,
or sulfite level (lowered) of
the condensate, feed water, or
boiler water.
|