|
Organic Water Treatment
Chemicals
Steam Boilers, Cooling Towers,
Hot And Chilled Closed Systems
Fuel Oil Treatment
(Home of D.M Concentrate)
Boilers
Questions & Answer
Question:
Emergency low boiler water level
You are an officer on watch,
& finds the boiler
water-level gauge glass to be
empty & the burner
firing...What is your course of
action? (Assuming the gauge
glass to be clear & good
working order)
Answer:
Normally a boiler is provided
with two independent sensors for
emergency low water level burner
cut-outs. So this would never
happen. However, if it does,
don't take any take chances!
Shut off the burners
immediately!
Before you start raising the
level in the boiler you have to
find out if any part of the
furnace walls has been
overheated. If you raise the
level over a glowing steel-wall
then the boiler might produce
more steam than the safety
valves can handle and a nasty
explosion would be the result.
Question: Differential
pressure transmitters for the
steam drum level
Way is the high pressure leg of
the transmitter connected to the
water side and the low-pressure
leg connected to the steam side?
Answer:
The signal from the transmitter
ought to increase when the water
level raises and decreases when
the level falls. Furthermore the
signal shall be zero, and give
impulse to stop the burner, in
case of transmitter malfunction,
power failure or cable
breakdown.
Both requirements will be
fulfilled if the transmitter is
mounted with the high pressure
measuring point connected below
the lowest water level and the
low pressure measuring point
connected above the highest
water level. The output will
increase when the level is
raised. To compensate for the
water column in the reference
leg the output signal's
zero-point has to be elevated.
This is the common method.
If the transmitter is swapped,
with the low pressure side to
lower end and the high pressure
side to upper end, then the
signal will decrease when the
level is raised.
This signal can be used to
control the level as well, but
the signal can not be used to
stop the burner for emergency
low level in case of power
failure or cable breakdown. This
system requires an extra sensor
to trip burner at emergency low
water level.
One can of course use the
emergency high water level alarm
to stop the burner, but this is
not correct. The emergency high
water level shall stop the feed
water pump and whenever
applicable stop the steam
turbine, but not the burner.
Question: Fluctuating boiler
water level
The feed water control valve is
fully open and the water levels
fluctuate at normal boiler load.
Answer:
Check if:
- the control
valve really is fully open
by means of the
hand-maneuver device.
- all stop
valves in the line are fully
open.
- the suction
filter to the feed water
pump is satisfactory clean.
- the feed
water pump discharge
pressure is sufficient.
- the feed
water control valve pressure
drop is normal. (>=2 bar
or >=30 psi)
If all these are
fund to be in order, then you
should recalculate the control
valves kV-value (CV-value).
Under-sized control valves do
exist, even though over-sized
control valves more often cause
malfunction of automatic control
loops.
The tuning of the controller (s)
is dependent on the system you
have, but do not even try to
tune the control loops until the
above criteria are fulfilled.
Question: The burner starts
and stops very often
The burner starts and stops very
often, sometimes every second
minute. An alarming
temperature-raise has been
observed in the combustion air
fans electric motor.
Answer:
- Increasing
the burners turn down ratio
would be a nice solution,
but it's not always
possibly.
- Run the
burner in minimum load,
i.e., prevent the burner
from increasing the load
just after the burner start.
- Install a
five to ten minutes'
time-delay in the fan-motor
stop function. Then the fan
will continue to run during
the shortest burner stops
and the combustion air fan
motor will get a little rest
from the start current.
Question: Most
likely source of errors
In which part of a boiler
control system is it most likely
to get a failure.
Answer:
When you have problem with a
boiler control system you should
keep in mind that most faults
occur outside the control
cubicle, but on the other hand,
your problem might not be among
the most common.
Statistically calculated
faults in control systems.
Transmitters and sensors 40 %
Actuators 25 %
Controllers 10 %
Loss of electric power 5 %
Others 20 %
Question: Open steam valves
slowly
Why has a steam valve, or at
least a big steam valve, to be
opened slowly?
Answer:
If you have a one liter of water
standing in the pipe just after
the valve and open the valve too
fast, then you will get a
projectile of one kg rushing
down the pipe. At next valve,
bend or other obstacle the speed
of the water mass will be
converted into pressure. You can
hardly imagine the damage this
energy can cause.
Thermal stress is an other
reason to be very cautious and
drain out water carefully when
you open a steam valve.
A large steam valve ought to
have a small by-pass valve to
simplify preheating of the pipe.
Question: Low viscosity fuel
for high viscosity burners
Our boiler plant is designed to
be fired with heavy fuel oil of
600 CST @ 50°C.
Would it be safe to run it on
Gas Oil of 7 CST @ 40°C?
Answer:
Well, this is a question for
the burner maker. Don't forget
to ask them too.
It is very important that the
fuel oil heaters are bypassed
when firing Gas Oil or Diesel
Oil. These fuels must never be
heated above their flash-point.
- For a steam
atomized burner you have to
switch over to compressed
air atomizing since light
fuels must not be atomized
by means of steam. This
burner will probably fire
the fuel without any problem
since they normally are
designed for fuel viscosity
between 10 and 20 CST.
- A rotary
cup burner, on the other
hand, might give some
problem with the flame since
this atomizing method
normally require a fuel
viscosity of about 25 to 60
CST.
In the event of
failed ignition, gas-oil is more
likely to cause an explosive
mixture than heavy oil. However,
a dangerous situation should
never occur if the procedure for
such failed ignition is
followed. Upon two consecutive
failed ignition attempts, a
thorough investigation into the
cause should be sought and the
furnace correctly purged inline
with the manufacturers and
ruling classification society's
requirements.
N.B. 7 CST @
40°C = 5.5 CST @ 50°C.
The
viscosity's of lighter fuels are
normally given at 40°C and the
viscosity of heavier fuels at 50°C,
80°C, 100°C or even higher
temperature.
|