PRODUCT USES:
Thermidaire Rltreat-901-H is a highly concentrated blend of
a special filming amine, three volatile neutralizing amines of low, medium and high distribution ratios,
the filming amine will prevent the formation of corrosion. Thermidaire
Rltreat-901-H specially
formulated to protect and inhibit condensate corrosion caused by
carbon dioxide and/or dissolved oxygen in steam and condensate return
lines, suited for complex steam systems, which include very short, short, medium and long - length
runs including boiler room equipment, in high pressure steam boilers
(900 to 1500 PSI) and will provide, inhibits corrosion in vapor-phase
processes and to cold-end equipment in the flue gas systems specially in
high efficiency installation which operate at or near condensation
conditions. Provides full protection for multi-stage turbines.
DESCRIPTION:
Physical State: Liquid
Colour: Light yellow
BENEFITS:
- Protects condensate return lines against channeling and
grooving corrosion.
- Protects and controls carbonic acid attack of pipe threads and
connections.
- Protects all condensate system metals against corrosion.
- Minimizes boiler iron deposits by reducing condensate
corrosion.
- Prevents costly unscheduled shout-downs and maintenance.
- Prevents corrosion due to dissolved CO2.
- Prevents corrosion due to dissolved O2.
- The filming amine will prevent the formation of corrosion.
- On site tests allow correct monitoring.
DOSAGE:
Thermidaire Rltreat-901-H dosage
is related to the amount and the quality of make-up water, if used for
the protection of the steam return lines and the condensate, the dosage
can be estimated at 10-15 PPM in the steam, when used as
vapor-phase process corrosion inhibitor, it can be estimated at 25-50
PPM in the steam, the dosage should be adjusted depending on the nature
of the operation. when
used as a flue-gas corrosion inhibitor, the dosage can be estimated at 1
gallon per 1000,000 cu ft of natural gas burned.. All guide lines for
boilers operating at 900 PSI and higher should apply.
FEEDING:
Thermidaire Rltreat-901-H can be fed by means of
dosing pump separately to the
deaerator storage section, feed-water tank, feed-water line, or
directly to the boiler steam header when used to protect steam
return line and the condensate.
Thermidaire Rltreat-901-H when used as vapor-phase process
corrosion inhibitor, it can be injected to the gas steam. after the
thermal deaerator can be fed with other boiler water
treatment chemicals.
HANDLING:
When handling, Thermidaire Rltreat-901-H, ware safety
glasses and protective gear., avoid contact with
skin and eyes. Should contact occur, flush immediately with plenty
of water. Avoid breathing vapor. Seek medical attention.
Consult the Material Safety Data Sheet before
handling this product and for complete handling and storage
information.
PACKAGING:
Thermidaire Rltreat-901-H is packaged in none-refundable
200 L drums.
|