SOFTENER SIZING FORMULA

C = M * T * H /R

C = Capacity of softener in cubic feet of resin

M = Makeup water volume per hour in gallons; the volume needed to be softened (8.34 pounds per gallon)

T = Time in hours desired between regeneration cycles

H = Hardness of water in grains (17.1 ppm per grain hardness)

R = Resin Capacity per cubic foot (this is virtually always 30,000 grains)