|
Bleed
Location in Cooling Systems
In
the cooling process, the greatest heat
dissipation is achieved by evaporating
droplets of water at the cooling
tower. As the water is evaporated, the
solids are left behind to concentrate.
We bleed a portion of the water to
control the water's chemistry.
The
bleed-off should be located downstream
of the condenser (heat exchanger) to
save energy. Bleed-off from this point
will remove warmer water and reduce
the cooling load.
For
example, assume we have a 300 Ton
tower, fully loaded with a 10 Deg F
drop across the tower. The system is
operating at four cycles of
concentration.
The
evaporation (E) and bleed-off (B)
rates are calculated as follows:
E = 300 tons x 3 gpm
/
ton x .01 = 9 gpm
B=
9 gpm (E)
/
4 cycles - 1
B = 3 gpm
By
bleeding off warm water, the tower
will become more efficient. We can
calculate the savings as follows:
Tons
Saved = Bleed-off (B) in gpm x the
density of water (8.34) x 1 BTU per
pound of water x the temperature drop
across the tower (oF) x 60 min/hr (
12,000 BTU/ton/hr
EXAMPLE:
Tons
Saved = 3 pg. x 8.34 lb/gal x 1 BTU/lb
x 10 oF x 60 min/hr ( 12,000
BTU/ton/hr = 1.2 tons
This
would be a savings of 0.4% [(1.2/300)
x 100]. This may not seem like much,
but one ton of air-conditioning will
cool approximately 750 ft. of office
space. Therefore, by locating the
bleed-off just after the condenser, we
could save 1.2 tons x 750 ft/ton or
900 square feet of air conditioned
office space. A 400 ton system
operating at three cycles of
concentration could save over 1,800
ft. of floor space.
|